PMS Airnet  (PMS)
OPC Server Data Sheet

Devices Supported: Particle Measuring Systems (PMS) devices:
- Airnet
- CLS-900
- CLS-1000
- HSLIS-E
- LASAIR II
- IsoAir PLUS
- Liquistat
- Aerosol Manifold II
- MiniNet
- Ultra DI
OPC Compliance: OPC 2.04 and OPC 1.0a Data Access
Platform: Windows NT4.0 / 2000 / XP
Interface Type: Ethernet
Protocol: PMS Ethernet Protocol
 
General Features
 
1 A user interface called the PowerTool for configuring channels, devices, and datablocks.  Statistical communications data is provided for throughput analysis at each level.
2 The PowerTool has a built-in datascope for checking t communications messages.  The PowerTool also has context sensitive help.
3 Supports the ability to read and write sensor configurations.
4 Automation Interface - You don't have to use the Power Tool to configure the driver.  You can make your own COM or OLE application (using Microsoft's Visual Basic) to configure the driver and access data. 
5 Secondary Poll Rate - The OPC Server polls a datablock at the secondary poll rate once the Access Time expires.  Data is polled at the secondary poll rate until there is another client request for data.  If  the secondary poll rate is set for a longer period of time than the Primary Rate, CPU resources are reduced while ensuring that the datablock will always be polled.
6 Phased Poll Rates
7 Enable/Disable individual communication channels, devices, and datablocks from the automation interface or your HMI.
 
Protocol Commands Supported
 
Protocol Command: Used to:
PMS_PAKT_MSG_RESET Reset a sensor.
PMS_PAKT_MSG_GET_CONFIG_INFO
PMS_PAKT_MSG_CONFIG_INFO
Read configuration data from the sensor.
PMS_PAKT_MSG_GET_STATUS
PMS_PAKT_MSG_STATUS
Read sensor status.
PMS_PAKT_MSG_DATE_TIME Synchronize sensor time to PC time.
PMS_PAKT_MSG_DATA Read sensro data.
PMS_PAKT_MSG_SET_CONFIG Write configuration data to the sensor.
PMS_PAKT_MSG_CONTROL Start and stop the sensor.
 
Signal Conditioning:
 
Signal Conditioning Name: Description:
NONE No Scaling
LIN (Unsigned) Scales 16-bit unsigned values to the database block's EGU range.
LIN (Signed) Scales 16-bit signed values to the database block's EGU range.
3BCD Scales 3-digit Binary Coded Decimal values to the database block's EGU range.
4BCD Scales 4-digit Binary Coded Decimal values to the database block's EGU range.
8BN Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. No Alarming on Out of Range.
8AL  Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. Alarming on Out of Range.
12BN Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). No Alarming on Out of Range.
12AL  Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). Alarming on Out of Range.
13BN Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. No Alarming on Out of Range.
13AL  Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. Alarming on Out of Range.
15BN Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. No Alarming on Out of Range.
15AL  Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. Alarming on Out of Range.