Home | OPC Servers and iFix Drivers | Universal OPC Server | Custom Work | Contact Info

Mettler-Toledo Digital Scales (M42)
Driver Data Sheet

Devices Supported: Mettler/Toledo Model 8142 Digital Scales, JN Port; Lynx Industrial Terminal, COM2 Port using RS232.
Device Manufacturer: Mettler-Toledo, Inc., 350 W. Wilson Bridge Rd., Worthington, Ohio 43085-2273.
Platform: Windows 95/98/NT/2000/XP
Interface Type: Serial: RS-232C
Max Devices Supported: One scale per COM port
Protocol: RS-232C Mettler/Toledo ASCII Command Input
Baud Rate: 1200, 2400, 4800, 9600
Data Bits: 7
Stop Bits: 1
Parity: EVEN
Contact: Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice:
(828) 635-7189, Fax: (828) 625-5319, E-Mail: , Web: http://dimension-software.com
 
Features
 
1. Supports Demand, Toledo Continuous or Toledo Short Continuous modes.
2. DBB Blocks can be configured to operate the CLEAR, PRINT, TARE, and ZERO keys from a FIX® VIEW screen.
3. Continuous Mode Status bytes (motion bit) can be accessed using DBB blocks.
4. DBB blocks have access to Gross, Net, and Tare weight and units.
 
Interface Modules
 
Model 8142 JN Port (RS-232C)
Lynx COM2 port
 
Commands Supported
M42 supports the following Mettler/Toledo commands:
 
C CLEAR
P PRINT
T TARE
Z ZERO
 
Signal Conditioning
NONE - Returns Raw Value
 