Siemens Power Meter (SPM)
Driver Data Sheet
Devices Supported: |
Model# |
Description |
|
4700 |
Power Meter |
|
4720 |
Power Meter (not supported by Windows 3.11) |
|
4300 |
Power Meter |
|
ISGS |
Intelligent SwitchGear System - firmware version V3 (not
supported by Windows 3.11) |
|
Static Trip III |
Trip Unit |
Device
Manufacturer: |
Siemens Corporation, 7000 Siemens Road, Wendell,
NC 27591. Tel: (919) 365-2200 x2435. FAX: (919) 365-6363. |
Reference
Docs: |
SIEMENS 4700 Power Meter SEAbus
Protocol Reference Manual No. SG-6363-00. |
|
SIEMENS 4720 Power Meter Protocol
Reference Manual No. SG-6373-00. |
|
SIEMENS 4300 Power Meter SEAbus
Plus Protocol Reference Manual No. SG-6353-01. |
|
SIEMENS ISGS Intelligent SwitchGear
System SEAbus Plus Protocol Reference Manual No. SG6413-00. |
|
SIEMENS Static Trip III SEAbus
Protocol Reference Manual No. SG6343-02. |
Platform: |
Windows 95/98/NT/2000/XP |
Interface Type: |
Serial (RS485 Network) |
Max Devices
Supported: |
32 |
Protocol: |
If the Device is a Model ... |
Then the Protocol Supported is ... |
|
4700 |
SEAbus |
|
4720 |
SEAbus |
|
4300 |
SEAbus Plus |
|
ISGS |
SEAbus Plus |
|
Static Trip III |
SEAbus |
Baud Rate: |
2400 - 38,400 |
Data Bits: |
8 |
Stop Bits: |
1 |
Parity: |
NONE |
Comment: |
The multidrop configuration allows a single
master (PC) and up to 32 slaves (Siemens Power Meter) on a single port. |
Contact: |
Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice: (828) 635-7189, Fax: (828) 625-5319,
E-Mail: ,
Web: http://dimension-software.com |
Device Manufacturer: |
Siemens Corporation |
Interface: |
Multidrop - RS-232 to RS-485 converter was used during testing. |
Comment: |
Also tested Telebyte Model 285 converter |
|
Commands Supported |
SPM supports the following commands: |
|
Table 1 Siemens 4700 Power Meter Commands Supported |
Message Code |
Description |
0Dh |
Request Time/Date |
07h |
Set Time/Date |
03h |
Read Long Real -Time Data |
1Bh |
Read Min Data Values |
1Ch |
Read and Clear Min Values |
1Ah |
Control Relays |
1Fh |
Clear Discrete Input Counter |
1Dh |
Read Max Data Values |
1Eh |
Read and Clear Max Data Values |
0Ah |
Read 4700 Setup Data |
0Bh |
Write Setup Data |
16h |
Clear KW Hours |
17h |
Clear KVAR Hours |
22h |
Read Waveform Data |
|
Table 2 Siemens 4300 Power Meter Commands Supported |
Message Code |
Description |
01h |
Read Setup Data |
02h |
Write Setup Data |
03h |
Read Real -Time Data |
04h |
Read Real - Time Data with Reset |
05h |
Clear Kilowatt Hours |
FFh |
Communications Version |
|
Table 3 Siemens 4720 Power Meter Commands Supported |
Message Code: 00h |
Valid DBB Block Types: AI, AA, AR (Read Only) |
Parameter |
I/O Address (DEV_NAME:MSG_CODE:BYTE_NO) |
Volts LN Average |
D43:00:01h |
Volts LN Phase A |
D43:00:05h |
Volts LN Phase B |
D43:00:09h |
Volts LN Phase C |
D43:00:0Dh |
Volts LL Average |
D43:00:11h |
Volts LL Phase AB |
D43:00:15h |
Volts LL Phase BC |
D43:00:19h |
Volts LL Phase CA |
D43:00:1Dh |
Amps Average |
D43:00:21h |
Amps Phase A |
D43:00:25h |
Amps Phase B |
D43:00:29h |
Amps Phase C |
D43:00:2Dh |
Amps Neutral |
D43:00:31h |
Volts Imbalance |
D43:00:35h |
Amps Imbalance |
D43:00:39h |
kW Total |
D43:00:3Dh |
kW Phase A |
D43:00:41h |
kW Phase B |
D43:00:45h |
kW Phase C |
D43:00:49h |
kVAR Total |
D43:00:4Dh |
kVAR Phase A |
D43:00:51h |
kVAR Phase B |
D43:00:55h |
kVAR Phase C |
D43:00:59h |
kVA Total |
D43:00:5Dh |
kVA Phase A |
D43:00:61h |
kVA Phase B |
D43:00:65h |
kVA Phase C |
D43:00:69h |
PF Total |
D43:00:6Dh |
PF Phase A |
D43:00:71h |
PF Phase B |
D43:00:75h |
PF Phase C |
D43:00:79h |
Frequency |
D43:00:7Dh |
|
Table 4 Siemens ISGS Commands Supported |
Message Code |
Description |
D2h |
Request for Long Summary - Reads all real - time data, such as input,
output, and log status as well as electrical information |
|
Table 5 Siemens Static Trip III Commands Supported |
Message Code |
Description |
2Eh |
Get Long Real-Time Data |
NONE |
Returns Raw Value |
LIN |
Value Scaled to EGUs |
3BCD |
3 Digit Binary Coded Decimal |
4BCD |
4 Digit Binary Coded Decimal |
6BCD |
6 Digit Binary Coded Decimal |
12BN |
12 Bit Binary Scaled to EGUs - No Alarming on Out of Range |
12AL |
12 Bit Binary Scaled to EGUs - Alarming on Out of Range |
15BN |
15 Bit Binary Scaled to EGUs - No Alarming on Out of Range |
15AL |
15 Bit Binary Scaled to EGUs - Alarming on Out of Range |
|
|