SMAR LD-301 Intelligent Pressure Transmitter (HART Protocol) (U01)
OPC Server Data Sheet

Devices Supported: Model LD-301Intelligent Pressure Transmitter with Control Capability
Device Manufacturer: SMAR
Profile Name: LD301.PRO
Profile Built For: UOS
Platform: Windows NT4.0 / 2000 / XP
Interface Type: Serial: RS232
Max Devices Supported: 15
Protocol: HART
Comment: U01 is comprised of the Universal OPC Server (UOS) for Serial and TCP/IP Devices and the LD301.PRO device profile. The U01 mnemonic is used to identify this unique combination. UOS will also support many other serial or TCP/IP device profiles. Please refer to our web site for the current list.
UOS is a stand-alone OPC Server that can be used with any OPC compliant Client such as Intellution’s FIX® or FIX Dynamics® or OA’s Enterprise Automation software. UOS has many advanced features like: DataView, DataScope, Serial and TCP/IP communications support, and multiple "different" device support. Please refer to our web site for more information on UOS capabilities.
Contact: Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice:
(828) 635-7189, Fax: (828) 625-5319, E-Mail: , Web: http://dimension-software.com
References:  UOS (Universal OPC Server) Electronic Documentation
 

Introduction

This document provides general information on the device commands supported by UOS and the LD301.PRO profile. If you have installed UOS, you should also review the sections titled About the I/O Driver, How Do I…, Setting up The I/O Driver, and Using the PowerTool in the UOS electronic documentation. To get there, click on Help and Help Topics on the PowerTool menu bar. The PowerTool is a client application with a graphical user interface that accesses the UOS OPC Server and lets you view and modify communications channel, device, and datablock properties.
 
Device Commands Supported
U01 I/O Driver supports the following device commands. Please refer to the HART Communications Protocol, Universal Command Specifications, Revision 5.1, Document Number: HCF-SPEC-127, pg 1 - 25 for detailed information on the universal command codes.
 
Table 1 Supported Universal Commands for the SMAR LD301 Pressure Transmitter using HARTSMAR.PRO Profile
Command Code Description

Universal Command Codes
0 Read unique identifier
1 Read primary variable
2 Read PV current and percent of range
3 Read dynamic variables and PV current
14 Read primary variable sensor information
15 Read primary variable output information
16 Read final assembly number
19 Write final assembly number
 
Table 2 Supported Device Specific Commands for the SMAR LD301 Pressure Transmitter using HARTSMAR.PRO Profile
Command Code Description
136 Read PID block configuration
137 Write PID block configuration
138 Read controller mode
139 Write controller mode
141 Write set point tracking and PID mode
142 Read PID block parameters
143 Write proportional factor (kp)
144 Write integral time (tr)
145 Write derivation time (td)
146 Write set point
147 Write manipulated variable (mv)
193 Read controller variables
 
Comment: This I/O Driver has the following special features:
Poll-on-Demand
Enable/Disable polling for a selected device
Diagnostics for each device instead of per-channel
Write multiple variables simultaneously
 
Protocol Supported:
Protocol Type: HART
Supported: N/A
Baud Rates: 1200
Data Bits: 8
Stop Bits: 1
Parity: ODD

Comment: The table below describes the Channel Setup settings for the HART protocol. The settings listed in the table were used during testing at DSI. They could vary depending on your particular application. The driver period should be set to 2.

 
Table 3 Channel Setup settings for the HART protocol
Field Setting Comments
  Hardware Setup Area  
Port User Choice  
Baud Rate 1200  
Data Bits 8  
Stop Bits 1  
Parity Odd  
Flow Control RTS Delay Refer to the Pre-RTS field.
  RTS Delay Area  
Pre-Transmit 0  
Post-Transmit 0  
Pre-RTS 100 The HART protocol requires a delay after sending a message to U01. 100msec was used during testing of the HARTSMAR.PRO profile.
  Error Handling Area  
Reply Timeout 2.0  
Delay 1.0  
Retries 3  
 
Interface Modules:
Device Manufacturer: ANSCO, PO Box 24069, Minneapolis MN 55424
Interface: PRIMM modem, Bell-202 modem for HART protocol, RS-232 port powered.
Comment: HART protocol devices such as the SMAR LD-301 Pressure Transmitter requires a modem between the computer serial port and the device network. A PRIMM modem manufactured by Ansco, Inc. was used during testing.
 
Signal Conditioning:
 
Signal Conditioning Name: Description:
NONE No Scaling
LIN (Unsigned) Scales 16-bit unsigned values to the database block's EGU range.
LIN (Signed) Scales 16-bit signed values to the database block's EGU range.
3BCD Scales 3-digit Binary Coded Decimal values to the database block's EGU range.
4BCD Scales 4-digit Binary Coded Decimal values to the database block's EGU range.
8BN Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. No Alarming on Out of Range.
8AL  Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. Alarming on Out of Range.
12BN Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). No Alarming on Out of Range.
12AL  Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). Alarming on Out of Range.
13BN Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. No Alarming on Out of Range.
13AL  Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. Alarming on Out of Range.
15BN Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. No Alarming on Out of Range.
15AL  Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. Alarming on Out of Range.
 