Yokogawa - UP550 Program Controller (U55)
OPC Server Data Sheet
Devices Supported: |
Yokogawa UP550 - Program Controller |
Device
Manufacturer: |
Yokogawa |
Profile Name: |
YK_UP550.PRO |
Profile Built For: |
UOS |
Platform: |
Windows NT4.0 / 2000 / XP |
Interface Type: |
Serial: RS-485 |
Max Devices
Supported: |
31 |
Protocol: |
YOKOGAWA |
Comment: |
U55 is comprised of the Universal OPC
Server (UOS) for Serial and TCP/IP Devices and the YK_UP550.PRO
device profile. The U55 mnemonic is used to identify this unique combination. UOS will
also support many other serial or TCP/IP device profiles. Please refer to our web site for
the current list. |
|
UOS is a stand-alone OPC Server that can be used with any OPC
compliant Client such as Intellutions FIX® or FIX Dynamics® or
OAs Enterprise Automation software. UOS has many advanced features like: DataView,
DataScope, Serial and TCP/IP communications support, and multiple "different"
device support. Please refer to our web site for more information on UOS capabilities. |
Contact: |
Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice: (828) 635-7189, Fax: (828) 625-5319,
E-Mail: ,
Web: http://dimension-software.com |
References: |
UOS (Universal OPC Server) Electronic
Documentation |
|
GREEN SERIES, Communication Functions. Manual Number IM
5D1D01-10E. UP750/UP550 Program Controller Functions. Manual Number TI 5E1B01E. |
|
Introduction
|
This document provides general information on the device commands supported by UOS and
the YK_UP550.PRO profile. If you have installed UOS, you should also review the sections
titled About the I/O Driver, How Do I
, Setting up The I/O Driver, and
Using the PowerTool in the UOS electronic documentation. To get there, click on Help
and Help Topics on the PowerTool menu bar. The PowerTool is a client application
with a graphical user interface that accesses the UOS OPC Server and lets you view and
modify communications channel, device, and datablock properties. |
|
Device
Manufacturer: |
Yokogawa Electric Corporation |
Interface: |
RS-485, 2-wire |
Comment: |
Telebyte Model 245 RS-232 to RS-422/RS-485 Interface Converter used during
testing. |
|
Device Commands Supported
|
U55 supports the following Yokogawa commands: |
|
Table 1 UP550 Yokogawa Function Codes Supported |
If the U550 Command Group is... |
Then the UP550 READ COMMAND is... |
Then the UP550 WRITE COMMAND is... |
AUTO_MAN (Read/Write Automatic/Manual Mode) |
WRD |
WWR |
INF (Model, Version, and Revision Read) |
INF |
n/a |
READ_WRD (Multiple Register/Relay Word-Unit Read) |
WRD |
n/a |
RW_WRD (Register/Relay Word-Unit Read and Write) |
WRD |
WWR |
READ_BRD (Multiple I Relay Bitwise Read) |
BRD |
n/a |
RW_BRD (I Relay Bitwise Read and Write) |
BRD |
BWR |
RW_BIT (Read/Write Bit) |
WRD |
WWR |
Protocol Type: |
YOKOGAWA |
Baud Rates: |
600, 1200, 2400, 4800, 9600, 19.2k, 38.4k |
Data Bits: |
8 |
Stop Bits: |
1 |
Parity: |
NONE |
Signal Conditioning
Name: |
Description: |
NONE |
No Scaling |
LIN (Unsigned) |
Scales 16-bit unsigned values to the database block's EGU
range. |
LIN (Signed) |
Scales 16-bit signed values to the database block's EGU
range. |
3BCD |
Scales 3-digit Binary Coded Decimal values to the database
block's EGU range. |
4BCD |
Scales 4-digit Binary Coded Decimal values to the database
block's EGU range. |
8BN |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. No Alarming on Out of Range. |
8AL |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. Alarming on Out of Range. |
12BN |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). No Alarming on Out of
Range. |
12AL |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). Alarming on Out of
Range. |
13BN |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. No Alarming on Out of Range. |
13AL |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. Alarming on Out of Range. |
15BN |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. No Alarming on Out of Range. |
15AL |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. Alarming on Out of Range. |
|
|