Sentinel 500 Gas Orifice Flow Computer (UFC)
OPC Server Data Sheet

Devices Supported: Sentinel 500 Gas Orifice FlowComputer (UFC)
Device Manufacturer: Daniel Europe LTD, Swinton Grange, Malton, North Yorkshire, Y017, United Kingdom
Profile Name: UFC.PRO
Profile Built For: UOS
Platform: Windows NT4.0 / 2000 / XP
Interface Type: RS-232
Baud Rates: 9600
Data Bits: 8
Stop Bits: 1
Parity: EVEN
Flow Control: RTS-Delay:   Pre-Transmit = 0, Post-Transmit = 0, Pre-RTS = 50
Max Devices Supported: 1
Protocol: Modbus Protocol (Modified)
Comment: UFC is comprised of the Universal OPC Server (UOS) for Serial and TCP/IP Devices and the UFC.PRO device profile. The UFC mnemonic is used to identify this unique combination. UOS will also support many other serial or TCP/IP device profiles. Please refer to our web site for the current list.
UOS is a stand-alone OPC Server that can be used with any OPC compliant Client such as Intellution’s FIX® or FIX Dynamics® or OA’s Enterprise Automation software. UOS has many advanced features like: DataView, DataScope, Serial and TCP/IP communications support, and multiple "different" device support. Please refer to our web site for more information on UOS capabilities.
Contact: Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice:
(828) 635-7189, Fax: (828) 625-5319, E-Mail: , Web: http://dimension-software.com
References:  UOS (Universal OPC Server) Electronic Documentation
 
Introduction

This document provides general information on the device commands supported by UOS and the UFC.PRO profile. If you have installed UOS, you should also review the sections titled About the I/O Driver, How Do I…, Setting up The I/O Driver, and Using the PowerTool in the UOS electronic documentation. To get there, click on Help and Help Topics on the PowerTool menu bar. The PowerTool is a client application with a graphical user interface that accesses the UOS OPC Server and lets you view and modify communications channel, device, and datablock properties.

 
Device Commands Supported
 
UFC supports the following commands:
If the Profile Command Group is… Then the Device READ command is… And the Device WRITE command is…

Description

M/S_STATUS/ALM 02 05 R Multiple W Single Alarm/Status
M/S_NUMERIC 03 10 R Multiple W Single Float
 
Signal Conditioning:
 
Signal Conditioning Name: Description:
NONE No Scaling
LIN (Unsigned) Scales 16-bit unsigned values to the database block's EGU range.
LIN (Signed) Scales 16-bit signed values to the database block's EGU range.
3BCD Scales 3-digit Binary Coded Decimal values to the database block's EGU range.
4BCD Scales 4-digit Binary Coded Decimal values to the database block's EGU range.
8BN Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. No Alarming on Out of Range.
8AL  Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. Alarming on Out of Range.
12BN Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). No Alarming on Out of Range.
12AL  Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). Alarming on Out of Range.
13BN Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. No Alarming on Out of Range.
13AL  Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. Alarming on Out of Range.
15BN Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. No Alarming on Out of Range.
15AL  Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. Alarming on Out of Range.
 
© 2011 Dimension Software, Inc. All Rights Reserved.