Home | OPC Servers and iFix Drivers | Universal OPC Server | Custom Work | Contact Info

Sartorius LP 6200 S Balance (ULP)
OPC Server Data Sheet

Devices Supported: Sartorius LP 6200 S Balance
Device Manufacturer: Sartorius AG Goettingen, Germany TEL: (551) 308-0 FAX: (551) 308-289
Profile Name: Sartorius_LP6200S.PRO
Profile Built For: UOS
Platform: Windows NT4.0 / 2000 / XP
Interface Type: RS-232
Max Devices Supported: 1
Protocol: Sartorius LP 6200 S Balance Protocol
Comment: ULP is comprised of the Universal OPC Server (UOS) and the Sartorius_LP6200S.pro device profile. The ULP mnemonic is used to identify this unique combination. UOS will also support many other devices that use serial communications. Please refer to our web site for the current list.
UOS is a stand-alone OPC Server that can be used with any OPC compliant Client such as Intellution’s FIX® or FIX Dynamics® or OA’s Enterprise Automation software. UOS has many advanced features like: DataView, DataScope, Serial and TCP/IP communications support, and multiple "different" device support. Please refer to our web site for more information on UOS capabilities.
Contact: Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice:
(828) 635-7189, Fax: (828) 625-5319, E-Mail: , Web: http://dimension-software.com
References:  UOS (Universal OPC Server) Electronic Documentation. This includes context sensitive documentation on UOS configuration and device dependent profile documentation.
Sartorius Master pro Series LP Models Electronic Precision Balances Operating Instructions. Technical Support: 1-800-635-2906
 
Introduction
This document provides general information on the device commands supported by UOS and the Sartorius_LP6200S.PRO profile. If you have installed UOS, you should also review the sections titled About the I/O Driver, How Do I…, Setting up The I/O Driver, and Using the PowerTool in the UOS electronic documentation. To get there, click on Help and Help Topics in the PowerTool menu bar. The PowerTool is a client application with a graphical user interface that accesses the UOS OPC Server and lets you view and modify communications channel, device, and datablock properties.
 
Device Commands Supported
The device commands supported are shown in Table 1. They are described in reference to the profile command group that contains them. A "profile command group" is a group of related commands. Usually it consists of an I/O Device READ/WRITE command pair. However the command group can contain only a device READ command, only a device WRITE command, or more than one device READ/WRITE pair. This depends on the protocol of the I/O Device to which the command is directed.
 
Table 1 - Device Commands Supported by the Sartorius_LP6200S. pro Profile

Profile Command Group Name

Description

PrintRaw Use this command group to Print the raw data weight displayed on the LP6200S Balance. The balance Level 7 (Print for Application) MUST be set to 7 2 1.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: P

Description: Read/Print weight and units displayed on balance display (Format 1 command)

PrintGLP Use this command group to Print the GLP data weight displayed on the LP6200S Balance. The balance Level 7 (Print for Application) MUST be set to 7 2 2.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: P

Description: Read/Print GLP weight and units displayed on balance (Format 1 command)

AutoPrint Use this command group to read unsolicited raw data weight displayed on the LP6200S Balance. The balance Level 6 (Print Manual/Automatic) MUST be set to 614, 615, or 616. The balance Level 7 (Print for Application) MUST be set to 7 2 1.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: None

Description: Unsolicited Weight Data

Tare Use this command group to Tare the LP6200S Balance. Using this TARE command performs the same action as pressing the TARE button on the balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: T

Description: Tare Balance (Format 1 command)

Restart Use this command group to Restart the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: S

Description: Restart Balance (Format 1 command)

Weighing_1 Use this command group to Set Weighing Mode 1 (min vib) on the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: K

Description: Set Weighing Mode 1 (Format 1 command)

Weighing_2 Use this command group to Set Weighing Mode 2 (norm vib) on the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: L

Description: Set Weighing Mode 2 (Format 1 command)

Weighing_3 Use this command group to Set Weighing Mode 3 (strong vib) on the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: M

Description: Set Weighing Mode 3 (Format 1 command)

Weighin_4 Use this command group to Set Weighing Mode 4 (extr vib) on the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: N

Description: Set Weighing Mode 4 (Format 1 command)

Tare_2 Use this command group to Tare the LP6200S Balance. Using this TARE command Taring is not possible when the gross weight is less than or equal to zero.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: f4

Description: Tare Balance (Format 2 command)

Zero Use this command group to Zero the LP6200S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: f3

Description: Zero Balance (Format 2 command)

PrintModel Use this command group to Print the Balance Model for the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: x1

Description: Print Balance Model (Format 2 command)

PrintSerial Use this command group to Print the Weighing Cell Serial Number for the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: x3

Description: Print Weighing Cell Serial Number (Format 2 command)

R/W_ID Use this command group to Print and set the ID Number for the LP6200S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: x5

Description: Read/Print ID number (Format 2 command)

Command: z5

Description: Set ID number (Format 3 command)

R/W_Weight Use this command group to Print and set the Weight Set Number for the LP6200S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: x6

Description: Read/Print Weight set number (Format 2 command)

Command: z6

Description: Set Weight Set number (Format 3 command)

R/W_Lot Use this command group to Print and set the Lot Number for the LP6200S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: x7

Description: Read/Print Lot number (Format 2 command)

Command: z7

Description: Set Lot number (Format 3 command)

TextInput Use this command group to Write a maximum of 8 text characters to the LP6200S Balance display. User must clear the display using the "F" function key or the "F" command group.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: t

Description: Text Input In Display (Format 3 command)

F_Key Use this command group create the same action as pressing the "F" Function Key for the LP 6200 S Balance.

SARTORIUS LP6200S COMMANDS USED IN THIS COMMAND GROUP:

Command: f2

Description: F Function Keyl (Format 2 command)

 
Signal Conditioning:
 
Signal Conditioning Name: Description:
NONE No Scaling
LIN (Unsigned) Scales 16-bit unsigned values to the database block's EGU range.
LIN (Signed) Scales 16-bit signed values to the database block's EGU range.
3BCD Scales 3-digit Binary Coded Decimal values to the database block's EGU range.
4BCD Scales 4-digit Binary Coded Decimal values to the database block's EGU range.
8BN Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. No Alarming on Out of Range.
8AL  Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. Alarming on Out of Range.
12BN Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). No Alarming on Out of Range.
12AL  Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). Alarming on Out of Range.
13BN Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. No Alarming on Out of Range.
13AL  Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. Alarming on Out of Range.
15BN Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. No Alarming on Out of Range.
15AL  Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. Alarming on Out of Range.
© 2011 Dimension Software, Inc. All Rights Reserved.