Dynalco Controls TM-5000 Universal Scanner (UTM)
OPC
Server Data Sheet
Devices Supported: |
Dynalco Controls TM-5000D and TM-5000E Universal Scanner |
Device Manufacturer: |
Dynalco Controls 3690 N.W 53rd Street Fort Lauderdale, FL
33309, Tel: (954) 739-4300 FAX: (954) 484-3376 |
Profile Name: |
TM5000.PRO |
Profile Built For: |
UOS |
Platform: |
Windows NT4.0 / 2000 / XP |
Interface Type: |
Serial: RS-232, RS-422. B & B Electronics RS-232 to
RS-422 converter model 422CON was used during testing. |
Max Devices Supported: |
31 on a RS-422 multi-drop network, 1 on RS-232 |
Protocol: |
Dynalco TM-5000 Protocol |
Comment: |
UTM is comprised of the Universal OPC
Server (UOS) for Serial and TCP/IP Devices and the TM5000.PRO device
profile. The UTM mnemonic is used to identify this unique combination. UOS will also
support many other serial or TCP/IP device profiles. Please refer to our web site for the
current list. |
|
UOS is a stand-alone OPC Server that can be used with any OPC
compliant Client such as Intellutions FIX® or FIX Dynamics® or
OAs Enterprise Automation software. UOS has many advanced features like: DataView,
DataScope, Serial and TCP/IP communications support, and multiple "different"
device support. Please refer to our web site for more information on UOS capabilities. |
Contact: |
Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice: (828) 635-7189, Fax: (828) 625-5319,
E-Mail: ,
Web: http://dimension-software.com |
References: |
UOS (Universal OPC Server) Electronic
Documentation |
|
Introduction
|
This document provides general information on the device commands supported by UOS and
the TM5000.PRO profile. If you have installed UOS, you should also review the sections
titled About the I/O Driver, How Do I
, Setting up The I/O Driver, and
Using the PowerTool in the UOS electronic documentation. To get there, click on Help
and Help Topics on the PowerTool menu bar. The PowerTool is a client application
with a graphical user interface that accesses the UOS OPC Server and lets you view and
modify communications channel, device, and datablock properties. |
|
Device Commands Supported
|
UTM supports the following Dynalco TM-5000 Protocol commands: |
|
Command |
Description |
L |
List All Setpoints |
C## |
Send Status of Channel ## |
K## |
Send Status of Channel ## |
S## |
Send Value of Setpoint ## |
T |
Delay Timer Value |
F |
First Out Alarm Information |
U |
Update All Channel Status |
V |
Scan All Channels Once |
Wake |
Ready Device for Initial Communication |
Protocol Type: |
Dynalco TM-5000 Protocol |
Baud Rates: |
300, 1200, 2400 |
Data Bits: |
8 |
Stop Bits: |
1 |
Parity: |
NONE |
Signal Conditioning
Name: |
Description: |
NONE |
No Scaling |
LIN (Unsigned) |
Scales 16-bit unsigned values to the database block's EGU
range. |
LIN (Signed) |
Scales 16-bit signed values to the database block's EGU
range. |
3BCD |
Scales 3-digit Binary Coded Decimal values to the database
block's EGU range. |
4BCD |
Scales 4-digit Binary Coded Decimal values to the database
block's EGU range. |
8BN |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. No Alarming on Out of Range. |
8AL |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. Alarming on Out of Range. |
12BN |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). No Alarming on Out of
Range. |
12AL |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). Alarming on Out of
Range. |
13BN |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. No Alarming on Out of Range. |
13AL |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. Alarming on Out of Range. |
15BN |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. No Alarming on Out of Range. |
15AL |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. Alarming on Out of Range. |
|
|