Watlow 988 1/8 DIN Microprocessor-Based Temperature/Process Controller
(UW8)
OPC Server Data Sheet
Devices Supported: |
988 Microprocessor-Based Temperature/Process Controller |
Device
Manufacturer: |
Watlow Controls , 1241 Bundy Blvd., Winona, Minnesota
55987-5580. Tel: (507)454-5300 Fax: (507)452-4507. |
Profile Name: |
WAT988.PRO |
Profile Built For: |
UOS |
Platform: |
Windows NT4.0 / 2000 / XP |
Interface Type: |
RS-485, RS-232 |
Max Devices
Supported: |
31 on an RS-485 Network, 1 on an RS-232 Network |
Protocol: |
ANSI X3.28 |
Baud Rates: |
9600 |
Data Bits: |
7 |
Stop Bits: |
1 |
Parity: |
ODD |
Comment: |
UW8 is comprised of the Universal OPC
Server (UOS) for Serial and TCP/IP Devices and the WAT988.PRO device
profile. The UW8 mnemonic is used to identify this unique combination. UOS will also
support many other serial or TCP/IP device profiles. Please refer to our web site for the
current list. |
|
UOS is a stand-alone OPC Server that can be used with any OPC
compliant Client such as Intellutions FIX® or FIX Dynamics® or
OAs Enterprise Automation software. UOS has many advanced features like: DataView,
DataScope, Serial and TCP/IP communications support, and multiple "different"
device support. Please refer to our web site for more information on UOS capabilities. |
Contact: |
Dimension Software, Inc.
1536 St. Clair Road, Taylorsville, NC 28681, USA
Voice: (828) 635-7189, Fax: (828) 625-5319,
E-Mail: ,
Web: http://dimension-software.com |
References: |
UOS (Universal OPC Server) Electronic
Documentation |
|
Introduction
|
This document provides general information on the device commands supported by UOS and
the WAT988.PRO profile. If you have installed UOS, you should also review the sections
titled About the I/O Driver, How Do I
, Setting up The I/O Driver, and
Using the PowerTool in the UOS electronic documentation. To get there, click on Help
and Help Topics on the PowerTool menu bar. The PowerTool is a client application
with a graphical user interface that accesses the UOS OPC Server and lets you view and
modify communications channel, device, and datablock properties. |
|
Device Commands Supported
|
UW8 supports the following commands: |
|
If the Profile Command Group is
|
Then the Device READ command is
|
And the Device WRITE command is
|
Description |
SP1 |
SP1 (?) |
SP1 (=) |
Read/Write Set Point 1 |
C1 |
C1 (?) |
N/A |
Read Input 1 Value |
ALM |
ALM (?) |
ALM (=) |
Read/Write Alarm Status |
CF |
CF (?) |
CF (=) |
Read/Write Degrees Select Display Loop |
ERR |
ERR (?) |
N/A |
Read/Write Error, Latching Enable |
ER2 |
ER2 (?) |
N/A |
Read/Write Error, Communications |
IN1 |
IN1 (?) |
IN1 (=) |
Read/Write Input 1 Type |
IT1A |
IT1A (?) |
IT1A (=) |
Read/Write Integral For Output 1, PID Set A |
LOC |
LOC (?) |
LOC (=) |
Read/Write Keyboard Lockout |
MDL |
MDL (?) |
N/A |
Read Model Number |
PB1A |
PB1A (?) |
PB1A (=) |
Read/Write Proportional Band Output 1, PID Set A |
PIDA |
PIDA (?) |
PIDA (=) |
Read/Write Lockout PID Set A, Menu |
RH1 |
RH1 (?) |
RH1 (=) |
Read/Write Range High Input 1 |
RL1 |
RL1 (?) |
RL (=) |
Read/Write Range Low Input 1 |
DFL |
DFL (?) |
DFL (=) |
Read/Write Default Unit Type |
RA1A |
RA1A (?) |
RA1A (=) |
Read/Write Rate Output 1, PID A |
RE1A |
RE1A (?) |
RE1A (=) |
Read/Write Reset Output 1, PID A |
Signal Conditioning
Name: |
Description: |
NONE |
No Scaling |
LIN (Unsigned) |
Scales 16-bit unsigned values to the database block's EGU
range. |
LIN (Signed) |
Scales 16-bit signed values to the database block's EGU
range. |
3BCD |
Scales 3-digit Binary Coded Decimal values to the database
block's EGU range. |
4BCD |
Scales 4-digit Binary Coded Decimal values to the database
block's EGU range. |
8BN |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. No Alarming on Out of Range. |
8AL |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. Alarming on Out of Range. |
12BN |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). No Alarming on Out of
Range. |
12AL |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). Alarming on Out of
Range. |
13BN |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. No Alarming on Out of Range. |
13AL |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. Alarming on Out of Range. |
15BN |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. No Alarming on Out of Range. |
15AL |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. Alarming on Out of Range. |
|
|
© 2011 Dimension Software, Inc. All Rights Reserved.
|
|
|
|
|